AGC

GCE-CGC-AGC_352A4

Applications

  • Small cold rooms
  • Commercial refrigeration cold rooms

Capacity Range

R1234yf: from 0,93 to 15,06 kW
R454C: from 0,85 to 13,8 kW
Accepted A2L refrigerants:
R455A
R454C
R1234yf
R1234ze

Attention

It is important to underscore that the safety measures for use of A2L refrigerants must comply with the provisions of the EN378 standard and the safety data sheets of the fluid used.

AGC

Overview

Our AGC cubic unit coolers are designed for installations that use the latest generation of A2L low GWP refrigerants. The units of this range are particularly compact and suitable for many types of applications, especially storage rooms for the preservation of fresh or frozen products.

Range consist of 57 customizable models

According to the room temperature the range is divided as follows:

  • AGC G4 E4 F4 A4 for higher temperatures (≥ +1 °C), with 4 mm fin spacing;
  • AGC G6 E6 F6 A6 or medium temperatures (≥ –15 °C), with 6 mm fin spacing, electric defrost version (ED) is recommended;
  • AGC G8 E8 F8 A8 for low temperatures (≥ –35 °C), with 8 mm fin spacing, equipped with electric defrost (ED).

On request the models can be equipped with non-standard: coils, defrosting and fan motors

Coil Features
AGC unit coolers are fitted with new concept highly efficient coils made from aluminum fins and special inner grooved copper tube. The particular coil geometry with a reduced inner volume means decreased refrigerant use. The coil design conforms to the regulations governing the reduction of HFCs with high greenhouse effect.
Casing
Casing Features Made of a magnesium aluminum alloy, with a smooth finish covered by a plastic protection film
Fan Motors
The standard AC fan motors employed have the following features:
  • Ø 250 mm
  • shaded pole single-phase 230V/1/50-60Hz
  • fiberglass charged polyamide fan guards
  • Ø 315 mm
  • external rotor single-phase 230V/1/50-60Hz
  • built-in electric capacitor
  • epoxy coated steel fan guard
  • Ø 350 mm
  • external rotor single-phase 230V/1/50-60Hz
  • built-in electric capacitor
  • epoxy coated steel fan guard

The optional high efficiency EC fan motors have the following features:
  • Ø 250 mm
  • single-phase 230V/1/50-60Hz
  • fibreglass charged polyamide fan guard
  • Ø 315 mm
  • external rotor single-phase 230V/1/50-60Hz
  • epoxy coated steel fan guard
  • Ø 350 mm
  • external rotor single-phase 230V/1/50-60Hz
  • epoxy coated steel fan guard
Defrost
The electric defrost (ED) versions are equipped with stainless steel heaters with vulcanised terminals preset for 400V/3/50-60Hz connections
Wiring
The electric parts and casework are connected to a grounding terminal The wiring of motors and heaters is carried out in separate IP 54 protection grade junction boxes.
Certifications
  • CE
  • PED
Published Data
  • EN 328 reference standard
  • Nominal capacity assessed in practical operating ambient i.e. in wet conditions
  • R1234yf and R454C refrigerants
  • air inlet temperature 0 °C
  • evaporating temperature –8 °C
  • TD 8 K

Contact Modine For More Information